DC OEM MODULE FOR USE WITH GERAPID CIRCUIT BREAKERS
APPENDIX B Primary Terminals Drawings.
2011-04-26 S47183Ee rev.01 Design and specifications are subject to change without notice 29
APPENDIX C – Layout drawings
Fig. C-1 Minimum required distances for installing the DC OEM Module
TOP VIEW :
Dimension A:
- min. 0.3 ft
Dimension B:
- min. 7 ft
Dimension C:
- min. 0.3 ft in case of no need for rear access,
- min. 1.5 ft in case of need for rear access.
NOTE: Minium free space over the Module’s roof should be 1.5 ft.
Trolley