DC OEM MODULE FOR USE WITH GERAPID CIRCUIT BREAKERS
APPENDIX G Accessories and Installation Drawings..
2011-04-26 S47183Ee rev.01 Design and specifications are subject to change without notice 39
APPENDIX F – Rating Tables
Breaker Rating Gerapid 2508
Gerapid 4008
Gerapid 5008 Gerapid 6008
Arc chute type 1x2 1x2 1x2 1x2
Rated continuous current 2,500 A 4,000 A 5,000 A 6,000 A
Rated short circuit peak/sustained current 200/120 kA 200/120 kA 200/120 kA 200/120 kA
Short circuit characteristics Duties a b, c, d Duties a b, c, d Duties a b, c, d Duties a b, c, d
Rated maximum system voltage 800 V 800 V 800 V 800 V
Power frequency withstand voltage 3,700 V / 60 sec 3,700 V / 60 sec 3,700 V / 60 sec 3,700 V / 60 sec
Maximum arc voltage 1,500 V 1,500 V 1,500 V 1,500 V
Mechanical endurance w/o maintenance* 20,000 cycles 20,000 cycles 20,000 cycles 20,000 cycles
Breaker weight 310 lbs 310 lbs 480 lbs 480 lbs
Table F-1 UL listed Gerapid Ratings according to IEEE Std. C37-14-2002
Module Rating DCOEM 4000
DCOEM 6000
Rated continuous current of the primary circuit 4,000 A 6,000 A
Type of Gerapid breaker for installation 2508 & 4008 5008 & 6008
Rated short circuit peak/sustained current 200/120 kA 200/120 kA
Rated maximum voltage 800 V 800 V
Rated insulation level of the primary circuit 5,200 V d.c. 5,200 V d.c.
Rated insulation level of the secondary circuits
1,500 V
1,500 V
Mechanical endurance w/o maintenance* 500 cycles 500 cycles
Weight of the trolley without Gerapid breaker 300 lbs 300 lbs
Weight of the Module without Trolley 550 lbs 580 lbs
Table F-2 UL listed DC OEM Module. Ratings according to IEEE Std. C37.20.1-2002
No functional parts replaced during the listed number of operations. Breakers require servicing at recommended intervals.
Servicing consists of adjusting, cleaning, lubricating, tightening and similar procedures as recommended in Users Guide