O-52 DC Brake Select
Option: Function:
Select control of the DC brake via the terminals (digital input) and/or via the network.
[0] Digit Input Activates command via a digital input.
[1] Bus Activates command via the serial communication port or network option module.
[2] Logic AND Activates command via the network/serial communication port, AND additionally via one of the digital
inputs.
[3] * Logic OR Activates command via the network/serial communication port OR via one of the digital inputs.
NB!
This parameter is active only when par. O-01 Control Site is set to [0] Digital and control word.
O-53 Start Select
Option: Function:
Select control of the drive start function via the terminals (digital input) and/or via the network.
[0] Digit Input Activates Start command via a digital input.
[1] Bus Activates Start command via the serial communication port or network option module.
[2] Logic AND Activates Start command via the network/serial communication port, AND additionally via one of the
digital inputs.
[3] * Logic OR Activates Start command via the network/serial communication port OR via one of the digital inputs.
NB!
This parameter is active only when par. O-01 Control Site is set to [0] Digital and control word.
O-54 Reversing Select
Option: Function:
[0] Digital Input Select control of the frequency converter reverse function via the terminals (digital input) and/or via the
network.
[1] Bus Activates the Reverse command via the serial communication port or network option module.
[2] Logic AND Activates the Reverse command via the network/serial communication port, AND additionally via one of
the digital inputs.
[3] * Logic OR Activates the Reverse command via the network/serial communication port OR via one of the digital
inputs.
NB!
This parameter is only active when par. O-01 Control Site is set to [0] Digital and control word.